PREMIER HYDROPHILIC

WATERSTOPS

(water swelling)

866.457.5710

Home About Adeka Contacts Technical Products Applications Brochures

- Easy Links -

Brochures - Contacts -  Products - Data Sheets - MSDS 

Chemical Resistance - Concrete Coverage 

Testing - Specification 

Copyright JL Miller 2012 - 866.457.5710

MC-2010MN

GENERAL USE - Cast-in-place non-moving joints.


REQUIREMENT - Minimum of 4" of 4300+ psi concrete on both sides of the waterstop (minimum 9" wall /slab). Place in the center between two rows of rebar. Wall height must be a minimum of 6.5 feet. This product will withstand a high hydrostatic head. OVER 700 FOOT HEAD IN LABORATORY TESTS.


Click on "installation instructions" for general installation information (pdf file).

MC-2005T

GENERAL USE: Cast-in-place joints with less than 50 foot hydrostatic head and less than 24" thick walls or slabs.

Follow same installment criteria as MC-2010MN. Click on "Ideal Installation Instructions" for more info (pdf file). Check data sheet for detailed information.


KBA-1510FP

GENERAL USE - Cast-in-place non-moving joints (less than 20' hydrostatic head).

Can be placed outside of rebar to protect rebar from moisture. Requires a minimum of 1.0" of 4300+ psi concrete coverage. Because of unknown concrete conditions we recommend 1.5" ~ 2.0" if possible. Excellent for 6" ~ 8" walls/slabs with single row of rebar or pins. Click on "Data Sheet" to view more detailed information.


MC-2010MN

P-201

Overlap (joint Segments)

Rough Concrete with P-201

Strip product with Adeka P-201 at corner joints